Audiology Suites are intended for clinical applications that require attenuating control and exam rooms. Eckel offers suites both in single wall configurations and double wall configurations. This offers a particular advantage when testing young children, so they can see their parents during testing. An Audiology Suite is designed to provide an environment for audiometric testing that meets the noise standards as set by the ANSI (American National Standards Institute). To meet these noise standards, many hospital and audiologists use Eckel Audiology Suites.
• 36” W x 73 3/4” H (914mm x 1873mm) Clear Opening Door
• 24” W x 30” H (610mm x 762mm) Window
• LED Lighting, and a Jack Panel complete with 12 1/4”
• Phone Jacks, 2 USB, and a 1” (25mm) pass-through
• HVAC COLLARS
• 20” X 60” (508mm x 1524mm) WINDOW IN DOOR
• ADDITIONAL DUPLEX OUTLETS
Wall & Ceiling Construction
Wall panels are 4” (100mm) and fabricated of galvanized solid steel outer surface and perforated steel inner surface. Ceiling panels include an integrated silenced ventilation system and 6” (150mm) thick with galvanized solid steel outer surface and perforated steel inner surface. Acoustic insulation is dependent on panels and designed to provide independently tested transmission loss of selected panel system.
Isolated Floor Construction
Floor panels are available in 2”, 3” and 4” (50.8mm, 76.2mm, 101.6mm) thick fabricated from galvanized steel outer and inner (walking) surfaces. The floor panels are supplied with heavy duty framing members and inner surface to support consistent use and accommodation for clients requiring wheelchair accessibility. Acoustic insulation is consistent with that of the wall and ceiling panels. All floors are installed
on isolation mounts to protect against structure borne noise sources. Overall step up height is approximately 7” (175mm) from outside.
Standard door clear openings are 36” W x 73 ¾” H. The doors are designed to provide similar acoustic performance as the walls and to sit flush when installed. Hardware consists of chrome plated hinges with a cam rise mechanism to ensure both proper seating of the door and ease of closing. A 1” (25mm) door pull handle is used, assuring ease of operation and ADA compliance. Door windows from small to full size are available as an option. Alternate door sizes can be accommodated.
Observation windows are provided, typical nominal size 24” (610mm) W x 30” (750mm) H, fabricated from two layers of laminated safety glass set in an extruded PVC window frame. Alternate sizes are available to suit specific needs.
All rooms are supplied with CSA approved, pre-wired 120 volts recessed internal electrical, including internal and external facing recessed hospital-grade duplex receptacles. Power is supplied via a power cord connected to the customer’s 120 volts source or may be hard-wired upon request. Country-specific electric and cord configurations are available for international customers (240v option also available).
Jack panels are installed on all rooms and suites both single and double wall. Standard jack panels are supplied with twelve .25” (6.3mm) phone jacks, two USB connections and one 1” (25mm) diameter pass-thru. Non-standard configurations are available to suit unique or specific jack requirements.
The integrated silenced ventilation system consists of factory installed extract air fans and a passive intake air flow.